Requirements for calculating battery capacity

 
   

SMU Series

Electrical Characteristics - Cell Performance Data

AMPERES TO FINAL VOLTAGE 1.65VPC AT 25ºC (77ºF)

CELL

TYPE

C8 AH

1.75

VPC

TIME

MINUTES

HOURS

1

5

10

15

20

30

40

1

2

3

5

8

10

12

20

SMU 200

200

541

419

355

300

257

201

170

125

75

56

38

26

22

19

11

SMU 300

300

812

629

533

450

386

302

255

188

112

83

56

39

33

28

17

SMU 500

500

1353

1048

888

750

643

503

425

313

187

139

94

65

55

46

29

SMU 600

600

1624

1258

1066

900

772

604

510

376

224

166

112

78

66

56

34

SMU 800

800

2164

1676

1420

1200

1028

804

680

500

300

224

152

104

88

76

44

SMU 1000

1000

2706

2096

1776

1500

1286

1006

850

626

374

278

188

130

110

92

58

SMU 1200

1200

3248

2516

2132

1800

1544

1208

1020

752

448

332

224

156

132

112

68

SMU 1500

1500

4059

3144

2664

2250

1929

1509

1275

939

561

417

282

195

165

138

87

SMU 1800

1800

4872

3774

3198

2700

2316

1812

1530

1128

672

498

336

234

198

168

102

SMU 2000

2000

5412

4192

3552

3000

2572

2012

1700

1252

748

556

376

260

220

184

116

SMU 2500

2500

6765

5240

4440

3750

3215

2515

2125

1565

935

695

470

325

275

230

145

SMU 3000

3000