PRODUCTS
Switchmode Batteries UPS Chargers Inverters
AUTOMATIC BATTERY CHARGER - P4 SERIES

FEATURES:

  • Proven design
  • Completely automatic
  • CSA / UL Standards
  • Convection Cooled
  • Low noise level
  • Reliable 15-20 year life
  • Input/output isolation
  • Full wave circuit design
  • Low deviation regulation
  • Soft Start
  • Protection against spikes,
    surges and overloads
  • Standard supervisory alarm panel
  • Quality Control to ISO9002-1994


Standard Floor Mount
P4 Charger

APPLICATIONS:

  • Utilities, Petrochemical, Industrial
  • Circuit breaker control & operation
  • Security/Monitoring/Signaling systems
  • Switchgear, Emergency lighting
  • Industrial process control
  • Engine starting batteries

Standard P4 48V 25A Charger

 
SUPERVISORY PANEL

Metering:  
·        
DC Voltmeter & Ammeter  
·        
2½" (63mm) scale, 2% FSD Accuracy

Indicating LED's:  
Control:  

·        
AC On (green)  
·        
Current Limit (green)  
·        
Voltage regulation (green)  
·        
Equalize (amber)  
·        
Float (green)  
Alarms:  

·        
Charger Fail (red)  
·        
High DC Volts (red)  
·        
Low DC Volts (red)  
·        
Ground Fault (red)  
·        
AC Fail (rd)  
·        
Buttons: LED's test  
Equalize
comes with 0-60Hrs and 0-60 day timers adjustable via dip switches  
Alarms
come with individual indicating LEDs and wired to common form "C" contacts  

Control:  
·         
FLOAT / EQUALIZE switch  
·         
FLOAT and EQUALIZE voltage potentiometers  
·         
CURRENT LIMIT potentiometer  
·         
BATTERY VOLTAGE THRESOLD potentiometer to adjust   Automatic Equalize initiation point  

Micro-processor control board

CABINET DIMENSIONS: OPTIONS AVAILABLE:

Model

Height

inches (mm)

Width inches (mm)

Depth inches (mm)

A-400

24 (610)

20 (508)

14 (356)

A-500

36 (914)

24 (610)

18 (457)

A-700

60 (1524)

36 (914)

24 (610)

A-1000

74 (1880)

24 (610)

28 (711)

A-1100

74 (1880)

32 (813)

28 (711)

A-1200

74 (1880)

38 (965)

28 (711)

A-1300

74 (1880)

46 (1168)

28 (711)

  • Cabinets can be oversized and provided with shelves for batteries
  • Steel Base to raise the cabinet to desired height
  • Special paint and NEMA/IP protection

Ø       Non-standard input voltage
Ø      
DC circuit breaker
Ø      
High capacity interrupting current CBs
Ø      
Battery circuit breaker
Ø      
Extended equalize timer with elapsed and remaining time indication
Ø      
Remote shutdown and equalize control
Ø      
Load shedding circuit
Ø      
Remote voltage sensing terminals
Ø      
High DC volts shutdown
Ø      
Individual alarm and breakers' contacts
Ø      
Audible alarm
Ø      
Manual voltage control
Ø      
Temperature compensated charging
Ø      
Load sharing circuit
Ø      
Extra output filtering
Ø      
50Hz or 400 kHz input frequency
Ø    
Tropicalization
Ø Distribution panel

STANDARD SPECIFICATIONS:

Input:
Standard Voltages
Phases
Frequency
Power Factor

Efficiency at full load

  • 110, 120, 208, 240, 380, 400, 480, and 600 VAC +/- 10%
  • 1 and 3 phase
  • 60 or 50 Hz +/- 5%
  • >0.75 (1 Phase),>0.80 (3 Phase)
  • >75% (1 Phase), >80% (3 Phase)

Output:
Standard Voltages
Power
AC Ripple Voltage
Static Regulation
 

Dynamic Regulation
  • 12, 24, 36, 48, 72, 125 and 250 VDC
  • From 60W to 25KW
  • <2% RMS when a charger is connected to a battery capacity 4 times its current rating
  • <1% for simultaneous variations of +/- 10% input voltage, +/- 5% input frequency and 0-100% load
  • <+/- 3% from 10% - 100% and 100% - 10% load variation (t<25mS)

Protection:
Overcurrent

Voltage Transients

  • Automatic current limiting circuit, adjustable from 30% to 100% of nominal rating input circuit breaker and output fuse
  • Surge suppression on input and output Reverse Polarity

Mechanical & Physical:
Enclosure:

Finish:

 

  • CEMA/NEMA 1(IP20), 2mm steel with hinged front door
  • Phosphatised and primed prior to painting with ASA61, light grey
  • Floor mounted models with 75mm (3") clearance at bottom to facilitate movement by lift truck, pallet jack or other

Environmental:
Audible noise
Operating temp. range

Operating humidity

  • 50 to 65 dBA at 1 meter (rating dependant)
  • -40°C to 50°C
  • Up to 95% (non-condensing)
STANDARD CABINETS:

General Legend

1

3 point latch & operated with a key locking handle

4

Screw for models A-300, 400, 500

2

Knock outs

5

Ventilation

3

Anchoring holes

6

Wall mounting holes

MODEL

A-1300

A

74"

1880mm

B

46"

1168mm

C

28"

711mm

D

22"

559mm

E

20"

500mm

F

3"

76mm

G

43"

1092mm


Notes

Protection

IP/20 NEMA1 Cabinets

Gauge

14 Gauge Steel

Colour #

ASA 61 Grey

Specifications Subject to Change Without Notice

MODEL

A-600

A-700

A-800

A

53"

1346mm

60"

1524mm

74"

1880mm

B

30"

750mm

36"

914mm

14"

356mm

C

18"

457mm

24"

610mm

28"

711mm

D

22"

559mm

22"

559mm

22"

559mm

E

12"

305mm

20"

500mm

20"

500mm

F

3"

76mm

3"

76mm

3"

76mm

G

27"

686mm

33"

838mm

11"

280mm